Technical Characteristics
- Parameter setting uses a tree-menu management system for easy checking and modification.
- Dynamic fault recording function, which facilitates identifying the cause of faults.
- Protection against overcurrent, three-phase current imbalance, overheating, phase loss, and motor overload.
- Supports BYOD standard Modbus communication protocol.
- Reasonably designed structure for easier installation and more convenient use; terminals are plug-type for easy wiring.
- Combines the drive board and main board into a single unit, reducing cost and simplifying operation.
Technical Features
- Main loop operating voltage: AC 380 V (±10%–15%)
- Main loop operating current: 40–1200 A
- Current limiting factor: 1.5–5.0 × Ie
- Main loop frequency: 50/60 Hz (±2%)
- Initial voltage: 25%–80% of Ue
- Cooling method: natural cooling
- Control loop power supply: 110–220 V ±15% (0.5 A) AC/DC
- Soft starting rise time: 1–120 s
- Communication method: RS485 serial communication
- Soft stop time: 0–60 s
- Maximum starting frequency: ≤10 starts per hour
Working principal
The main circuit of the SSD1 reduced voltage soft starter uses six SCRs (connected in anti-parallel series) to interface with the stator circuit of an AC motor. Based on the function of the SCR as an electronic switch, the soft starter employs a microprocessor to adjust the trigger angle, thereby changing the SCR conduction angle and controlling the motor input voltage to achieve a soft start. Once the start is complete, the output of the soft starter reaches the rated voltage. Then, the contactor or KM controlling the three-phase bypass closes, allowing the motor to operate directly on the grid.

Voltage Mode
![]() |
This parameter is used to determine the initial motor torque (when the frequency is constant, motor torque is proportional to the square of the applied voltage). Setup range:30%–80%. When adjusting this parameter, the user must consider both current and mechanical impact. If the value is too high, it will result in a very large initial current, causing excessive electrical and mechanical stress. In voltage-control mode, the current will vary according to the load. However, if the maximum current is limited to five times the rated current, the user can increase the start time to reduce the starting current. When the load is light or no-load, the motor can still complete the start process even if the setup rise time is not fully reached, due to the motor's stored kinetic energy accelerating its startup. |
Limit Current Start
![]() |
Maximum Permitted Current during Motor Start. Setup range:150–500% FLA (motor rated current). For an extended range, please contact the manufacturer. If the setup value is too high, the motor will draw excessive current from the main circuit to accelerate. If the setup value is too low, the motor may not reach full speed after completing the acceleration process. To help the start current quickly reach the set limit, it is recommended to use a shorter start time. |
Product Specification
|
SSD1 Soft Starter 380V (+10%~15%)50/60Hz(±2%) |
|||
|
Structural |
Product Model |
Rated Current le(A) |
Applicable Motor Rated Power(kW) |
|
M1 |
SSD1-40-E/C |
40 |
22 |
|
SSD1-54-E/C |
54 |
30 |
|
|
SSD1-68-E/C |
68 |
37 |
|
|
SSD1-80-E/C |
80 |
45 |
|
|
SSD1-100-E/C |
100 |
55 |
|
|
M2 |
SSD1-135-E/C |
135 |
75 |
|
SSD1-160-E/C |
160 |
90 |
|
|
SSD1-200-E/C |
200 |
115 |
|
|
SSD1-250-E/C |
250 |
132 |
|
|
SSD1-300-E/C |
300 |
160 |
|
|
M3 |
SSD1-360-E/C |
360 |
200 |
|
SSD1-500-E/C |
500 |
250 |
|
|
SSD1-640-E/C |
640 |
320 |
|
|
M4 |
SSD1-800-E/C |
800 |
400 |
|
SSD1-1000-E/C |
1000 |
500 |
|
|
SSD1-1200-E/C |
1200 |
600 |
|
Instruction for Product Model

Notice for Model Selection
- The soft starter must supply torque greater than the load torque to complete the start of equipment such as pumps and centrifugal pumps.
- Single start with constant load:** Permitted startup time is 40 s under 3 times the limited current, and 25 s under 4 times the limited current.
- Repeated starts:** If the motor is started 10 times per hour, the permitted startup time is 25 s under 3 times the limited current, and 15 s under 4 times the limited current. The corresponding thermal protection class is Class 10.
- Starting heavy-load motors:** Motors such as ball mill fans can be started up to 5 times per hour. If the limited current values are as above, the thermal protection class is Class 20. For higher startup frequencies, a higher power-level product must be used.
Motor and system protection functions
The SSD1 series reduced voltage soft starter provides multiple protections for both the motor and the soft starter. The main functions are as follows:
1. Phase failure protection:The soft starter will not start unless all three phases of the main power supply are present and the load is connected.
2. Overheat protection: Monitors temperature. Frequent starts can cause the SCRs to overheat (above 80 °C).
3. Overlong start time protection: Excessive start time is harmful to both the motor and the soft starter. The default start time limit is 30 s. Users can set this time between 10 and 300 s according to the actual load.
4. Overcurrent (timing limit) protection: If the current exceeds 5–8 times the rated value (configurable), the output will be cut off within 20–200 ms (configurable).
5. Inverse overload protection: Provides four levels of stall protection curves.
6. Light-load alarm: Trips protection and issues a frequency error alarm.
7. Frequency error alarm: Monitors and signals abnormal frequency conditions.
Outside Wiring Drawing

Instruction
1. Main circuit wiring
Terminals R, S, and T connect to the power supply; terminals U, V, and W connect to the motor.
2. Control power supply wiring
Connect to control power supply terminals D1 and D2.
3. Ground wiring
Connect to power supply terminal D3.
4. Bypass and output contacts
K3 controls the bypass contactor; K2 provides fault output; K1 provides running output. All are normally open contacts.
5.Start/stop control loop wiring
Connect control loop terminals P1, P2, and P3 according to the circuit diagram.
6. P4 is programmable input terminal.
7. A5 and A6 are 4-20mA analogue signal output terminals.
8. A1,A2,A3,and A4 are RS485 communication terminals.
Typical Application
The SSD1 series reduced voltage soft starter can be widely applied in electric power, metallurgy, petroleum, petrochemical, mining, chemical, construction, building materials, municipal projects, defense industry, light industry, textiles, printing and dyeing, paper, pharmaceuticals, and other sectors.
Pump
Use the soft stop function to reduce the impact of water hammer, thereby lowering system maintenance costs.
Ball mill
Use the voltage ramp startup to reduce gear torque friction, thereby saving time and costs.
Fan
Reduce belt friction and mechanical wear to lower maintenance costs.
Compressor
Use the current limitation function to achieve a smooth startup, thereby reducing motor heating and extending its service life.
Conveyor
Use soft start to achieve a smooth and gradual startup process, preventing product movement and liquid overflow.
![]() |
![]() |
![]() |