High voltage soft start fault description table |
|||
|
Fault number |
Fault Code |
Fault content |
Fault Description |
|
1 |
pc |
Drive protection |
|
|
2 |
ou |
Overvoltage |
After the SCR trigger fails, the overvoltage self-trigger reaches the set number of times (n619 setting value) |
|
3 |
Lu2 |
Grid power loss |
The three-phase power supply of the grid is disconnected (during soft start operation) |
|
4 |
oh |
Heat sink/radiator overheating |
The maximum value of the three-phase Heat sink/radiator exceed the set temperature (n601 set value) |
|
5 |
old |
Overload |
The load is too heavy or the parameter setting is too low (valid during bypass operation) |
|
6 |
ou2 |
Software overvoltage |
The number of overvoltage times reaches the set value |
|
11 |
Urr |
Voltage imbalance / Unequal voltage / |
When the SCR is in static state, the maximum voltage minus the minimum voltage across the SCR in the same power component exceeds the setting value of parameter n617. |
|
12 |
CE |
Serial communication error |
Modbus_RTU communication is abnormal. Check whether the communication parameters of the master and slave stations match. |
|
14 |
E |
RC current protection |
When the SCR is in static state, the difference between the maximum and minimum RC currents in the same component exceeds the setting value of parameter n618, and there is a problem with the voltage balancing or the grid harmonics are too large. |
|
15 |
Err |
EEROM parameter error |
Parameter out of bounds |
|
16 |
CT |
Current transformer open circuit |
The PT secondary circuit is open, and the current sensor output signal is judged after running for 200ms. |
|
17 |
rnd |
Earthing/Grounding protection |
The zero sequence current exceeds 25% of the setting value of parameter nP31 |
|
25 |
1HF1 |
A1 Fiber optic communication interruption |
The optical fiber receiving circuit of the main control board is disconnected. Check whether the optical fiber is disconnected, whether the power board is normal, and whether the driver board is normal. |
|
26 |
1HF2 |
A2 Fiber optic communication interruption |
Same as above |
|
27 |
1HF3 |
A3 Fiber optic communication interruption |
Same as above |
|
28 |
1HF4 |
A4 Fiber optic communication interruption |
Same as above |
|
29 |
1HF5 |
A5 Fiber optic communication interruption |
Same as above |
|
30 |
1HF6 |
A6 Fiber optic communication interruption |
Same as above |
|
31 |
1HF7 |
A7 Fiber optic communication interruption |
Same as above |
|
32 |
1HF8 |
A8 Fiber optic communication interrupted |
Same as above |
|
33 |
1HF9 |
A9 Fiber optic communication interruption |
Same as above |
|
34 |
1HFA |
A10 Fiber optic communication interruption |
Same as above |
|
35 |
2HF1 |
B1 fiber optic communication interruption |
Same as above |
|
36 |
2HF2 |
B2 fiber optic communication interruption |
Same as above |
|
37 |
2HF3 |
B3 Fiber optic communication interruption |
Same as above |
|
38 |
2HF4 |
B4 Fiber optic communication interruption |
Same as above |
|
39 |
2HF5 |
B5 Fiber optic communication interruption |
Same as above |
|
40 |
2HF6 |
B6 Fiber optic communication interruption |
Same as above |
|
41 |
2HF7 |
B7 Fiber optic communication interruption |
Same as above |
|
42 |
2HF8 |
B8 Fiber optic communication interrupted |
Same as above |
|
43 |
2HF9 |
B9 fiber optic communication interruption |
Same as above |
|
44 |
2HFA |
B10 Fiber optic communication interruption |
Same as above |
|
45 |
3HF1 |
C1 fiber optic communication interruption |
Same as above |
|
46 |
3HF2 |
C2 fiber optic communication interruption |
Same as above |
|
47 |
3HF3 |
C3 fiber optic communication interruption |
Same as above |
|
48 |
3HF4 |
C4 fiber optic communication interruption |
Same as above |
|
49 |
3HF5 |
C5 fiber optic communication interruption |
Same as above |
|
50 |
3HF6 |
C6 Fiber optic communication interruption |
Same as above |
|
51 |
3HF7 |
C7 fiber optic communication interruption |
Same as above |
|
52 |
3HF8 |
C8 fiber optic communication interruption |
Same as above |
|
53 |
3HF9 |
C9 fiber optic communication interruption |
Same as above |
|
54 |
3HFA |
C10 Fiber optic communication interruption |
Same as above |
|
55 |
Ab1 |
Current imbalance |
The three-phase current imbalance exceeds the set value |
|
56 |
Ab2 |
Voltage imbalance |
The three-phase voltage imbalance exceeds the set value |
|
60 |
1PE1 |
A1 thyristor/SCR failure protection |
When the SCR is static, the voltage across the SCR is lower than the value set by parameter n614. Check whether the current SCR is broken down. |
|
61 |
1PE2 |
A2 thyristor failure protection |
Same as above |
|
62 |
1PE3 |
A3 thyristor failure protection |
Same as above |
|
63 |
1PE4 |
A4 thyristor failure protection |
Same as above |
|
64 |
1PE5 |
A5 thyristor failure protection |
Same as above |
|
65 |
1PE6 |
A6 thyristor failure protection |
Same as above |
|
66 |
1PE7 |
A7 thyristor failure protection |
Same as above |
|
67 |
1PE8 |
A8 thyristor failure protection |
Same as above |
|
68 |
1PE9 |
A9 thyristor failure protection |
Same as above |
|
69 |
1PEA |
A10 thyristor failure protection |
Same as above |
|
70 |
2PE1 |
B1 thyristor failure protection |
Same as above |
|
71 |
2PE2 |
B2 thyristor failure protection |
Same as above |
|
72 |
2PE3 |
B3 thyristor failure protection |
Same as above |
|
73 |
2PE4 |
B4 thyristor failure protection |
Same as above |
|
74 |
2PE5 |
B5 thyristor failure protection |
Same as above |
|
75 |
2PE6 |
B6 thyristor failure protection |
Same as above |
|
76 |
2PE7 |
B7 thyristor failure protection |
Same as above |
|
77 |
2PE8 |
B8 thyristor failure protection |
Same as above |
|
78 |
2PE9 |
B9 thyristor failure protection |
Same as above |
|
79 |
2PEA |
B10 thyristor failure protection |
Same as above |
|
80 |
3PE1 |
C1 thyristor failure protection |
Same as above |
|
81 |
3PE2 |
C2 thyristor failure protection |
Same as above |
|
82 |
3PE3 |
C3 thyristor failure protection |
Same as above |
|
83 |
3PE4 |
C4 thyristor failure protection |
Same as above |
|
84 |
3PE5 |
C5 thyristor failure protection |
Same as above |
|
85 |
3PE6 |
C6 thyristor failure protection |
Same as above |
|
86 |
3PE7 |
C7 thyristor failure protection |
Same as above |
|
87 |
3PE8 |
C8 thyristor failure protection |
Same as above |
|
88 |
3PE9 |
C9 thyristor failure protection |
Same as above |
|
89 |
3PEA |
C10 thyristor failure protection |
Same as above |
|
90 |
Err1 |
External fault 1 |
External fault action defined by multi-function input terminal |
|
91 |
Err2 |
External fault 2 |
Same as above |
|
92 |
Err3 |
External fault 3 |
Same as above |
|
93 |
Err4 |
External fault 4 |
Same as above |
|
94 |
Err5 |
External fault 5 |
Same as above |
|
95 |
Err6 |
External fault 6 |
Same as above |
|
96 |
Err7 |
External fault 7 |
Same as above |
|
97 |
Err8 |
External fault 8 |
Same as above |
|
98 |
Err9 |
External fault 9 |
Same as above |
|
99 |
ErrA |
External fault 10 |
Same as above |
|
106 |
LuA |
Phase A input undervoltage |
Phase A input voltage is lower than the n605 setting value. Check the input power supply or voltage sampling circuit. |
|
107 |
LuB |
Phase B input undervoltage |
Phase B input voltage is lower than the set value of n605. Check the input power supply or voltage sampling circuit. |
|
108 |
LuC |
Phase C input undervoltage |
Phase C input voltage is lower than the set value of n605. Check the input power supply or voltage sampling circuit. |
|
109 |
ScA |
Phase A overcurrent |
Phase A overcurrent, action value (n607 * n302) |
|
110 |
ScB |
Phase B overcurrent |
Phase B overcurrent, action value (n607 * n302) |
|
111 |
ScC |
Phase C overcurrent |
Phase C overcurrent, action value (n607 * n302) |
|
112 |
LPA |
Phase A lost |
Phase A lost. Check the main circuit connection point or voltage sampling circuit. |
|
113 |
LPB |
Phase B lost |
Phase B is missing, check the main circuit connection point or voltage sampling circuit |
|
114 |
LPC |
Phase C lost |
Phase C is missing. Check the main circuit connection point or voltage sampling circuit. |
|
115 |
TR1 |
Phase A trigger failure |
The number of SCR trigger failures in phase A exceeds the setting value of parameter n603 |
|
116 |
TR2 |
Phase B trigger failure |
The number of SCR trigger failures of phase B exceeds the setting value of parameter n603 |
|
117 |
TR3 |
Phase C trigger failure |
The number of SCR trigger failures of phase C exceeds the setting value of parameter n603 |
|
118 |
Fed1 |
Phase A conduction feedback error |
In the standby state, the phase deviation of the feedback signal is too large. Check the optical fiber feedback position, voltage sampling connection position or the corresponding phase driver board feedback signal. |
|
119 |
Fed2 |
Phase B conduction feedback error |
Same as above |
|
120 |
Fed3 |
Phase C conduction feedback error |
Same as above |
|
121 |
Trp |
Trigger board power supply abnormality |
The trigger board control power supply is out of the range of DC22.0V~42.0V |
|
122 |
Tend |
Start timeout protection |
The startup time exceeds the setting value of parameter n616 |
|
123 |
JCEr |
Bypass contactor failure |
The bypass contactor closing coil current is greater than the nP37 setting value for more than 3 seconds. |
|
124 |
ACOU |
Grid overvoltage |
The grid voltage exceeds the protection value (1.15 times the rated voltage) |