Alarm Code Lookup Tool

High voltage soft start fault description table

Fault number

Fault Code

Fault content

Fault Description

1

pc

Drive protection

 

2

ou

Overvoltage

After the SCR trigger fails, the overvoltage self-trigger reaches the set number of times (n619 setting value)

3

Lu2

Grid power loss

The three-phase power supply of the grid is disconnected (during soft start operation)

4

oh

Heat sink/radiator overheating

The maximum value of the three-phase Heat sink/radiator exceed the set temperature (n601 set value)

5

old

Overload

The load is too heavy or the parameter setting is too low (valid during bypass operation)

6

ou2

Software overvoltage

The number of overvoltage times reaches the set value

11

Urr

Voltage imbalance / Unequal voltage /
Abnormal voltage equalization

When the SCR is in static state, the maximum voltage minus the minimum voltage across the SCR in the same power component exceeds the setting value of parameter n617.

12

CE

Serial communication error

Modbus_RTU communication is abnormal. Check whether the communication parameters of the master and slave stations match.

14

E

RC current protection

When the SCR is in static state, the difference between the maximum and minimum RC currents in the same component exceeds the setting value of parameter n618, and there is a problem with the voltage balancing or the grid harmonics are too large.

15

Err

EEROM parameter error

Parameter out of bounds

16

CT

Current transformer open circuit

The PT secondary circuit is open, and the current sensor output signal is judged after running for 200ms.

17

rnd

Earthing/Grounding protection

The zero sequence current exceeds 25% of the setting value of parameter nP31

25

1HF1

A1 Fiber optic communication interruption

The optical fiber receiving circuit of the main control board is disconnected. Check whether the optical fiber is disconnected, whether the power board is normal, and whether the driver board is normal.

26

1HF2

A2 Fiber optic communication interruption

Same as above

27

1HF3

A3 Fiber optic communication interruption

Same as above

28

1HF4

A4 Fiber optic communication interruption

Same as above

29

1HF5

A5 Fiber optic communication interruption

Same as above

30

1HF6

A6 Fiber optic communication interruption

Same as above

31

1HF7

A7 Fiber optic communication interruption

Same as above

32

1HF8

A8 Fiber optic communication interrupted

Same as above

33

1HF9

A9 Fiber optic communication interruption

Same as above

34

1HFA

A10 Fiber optic communication interruption

Same as above

35

2HF1

B1 fiber optic communication interruption

Same as above

36

2HF2

B2 fiber optic communication interruption

Same as above

37

2HF3

B3 Fiber optic communication interruption

Same as above

38

2HF4

B4 Fiber optic communication interruption

Same as above

39

2HF5

B5 Fiber optic communication interruption

Same as above

40

2HF6

B6 Fiber optic communication interruption

Same as above

41

2HF7

B7 Fiber optic communication interruption

Same as above

42

2HF8

B8 Fiber optic communication interrupted

Same as above

43

2HF9

B9 fiber optic communication interruption

Same as above

44

2HFA

B10 Fiber optic communication interruption

Same as above

45

3HF1

C1 fiber optic communication interruption

Same as above

46

3HF2

C2 fiber optic communication interruption

Same as above

47

3HF3

C3 fiber optic communication interruption

Same as above

48

3HF4

C4 fiber optic communication interruption

Same as above

49

3HF5

C5 fiber optic communication interruption

Same as above

50

3HF6

C6 Fiber optic communication interruption

Same as above

51

3HF7

C7 fiber optic communication interruption

Same as above

52

3HF8

C8 fiber optic communication interruption

Same as above

53

3HF9

C9 fiber optic communication interruption

Same as above

54

3HFA

C10 Fiber optic communication interruption

Same as above

55

Ab1

Current imbalance

The three-phase current imbalance exceeds the set value

56

Ab2

Voltage imbalance

The three-phase voltage imbalance exceeds the set value

60

1PE1

A1 thyristor/SCR failure protection

When the SCR is static, the voltage across the SCR is lower than the value set by parameter n614. Check whether the current SCR is broken down.

61

1PE2

A2 thyristor failure protection

Same as above

62

1PE3

A3 thyristor failure protection

Same as above

63

1PE4

A4 thyristor failure protection

Same as above

64

1PE5

A5 thyristor failure protection

Same as above

65

1PE6

A6 thyristor failure protection

Same as above

66

1PE7

A7 thyristor failure protection

Same as above

67

1PE8

A8 thyristor failure protection

Same as above

68

1PE9

A9 thyristor failure protection

Same as above

69

1PEA

A10 thyristor failure protection

Same as above

70

2PE1

B1 thyristor failure protection

Same as above

71

2PE2

B2 thyristor failure protection

Same as above

72

2PE3

B3 thyristor failure protection

Same as above

73

2PE4

B4 thyristor failure protection

Same as above

74

2PE5

B5 thyristor failure protection

Same as above

75

2PE6

B6 thyristor failure protection

Same as above

76

2PE7

B7 thyristor failure protection

Same as above

77

2PE8

B8 thyristor failure protection

Same as above

78

2PE9

B9 thyristor failure protection

Same as above

79

2PEA

B10 thyristor failure protection

Same as above

80

3PE1

C1 thyristor failure protection

Same as above

81

3PE2

C2 thyristor failure protection

Same as above

82

3PE3

C3 thyristor failure protection

Same as above

83

3PE4

C4 thyristor failure protection

Same as above

84

3PE5

C5 thyristor failure protection

Same as above

85

3PE6

C6 thyristor failure protection

Same as above

86

3PE7

C7 thyristor failure protection

Same as above

87

3PE8

C8 thyristor failure protection

Same as above

88

3PE9

C9 thyristor failure protection

Same as above

89

3PEA

C10 thyristor failure protection

Same as above

90

Err1

External fault 1

External fault action defined by multi-function input terminal

91

Err2

External fault 2

Same as above

92

Err3

External fault 3

Same as above

93

Err4

External fault 4

Same as above

94

Err5

External fault 5

Same as above

95

Err6

External fault 6

Same as above

96

Err7

External fault 7

Same as above

97

Err8

External fault 8

Same as above

98

Err9

External fault 9

Same as above

99

ErrA

External fault 10

Same as above

106

LuA

Phase A input undervoltage

Phase A input voltage is lower than the n605 setting value. Check the input power supply or voltage sampling circuit.

107

LuB

Phase B input undervoltage

Phase B input voltage is lower than the set value of n605. Check the input power supply or voltage sampling circuit.

108

LuC

Phase C input undervoltage

Phase C input voltage is lower than the set value of n605. Check the input power supply or voltage sampling circuit.

109

ScA

Phase A overcurrent

Phase A overcurrent, action value (n607 * n302)

110

ScB

Phase B overcurrent

Phase B overcurrent, action value (n607 * n302)

111

ScC

Phase C overcurrent

Phase C overcurrent, action value (n607 * n302)

112

LPA

Phase A lost

Phase A lost. Check the main circuit connection point or voltage sampling circuit.

113

LPB

Phase B lost

Phase B is missing, check the main circuit connection point or voltage sampling circuit

114

LPC

Phase C lost

Phase C is missing. Check the main circuit connection point or voltage sampling circuit.

115

TR1

Phase A trigger failure

The number of SCR trigger failures in phase A exceeds the setting value of parameter n603

116

TR2

Phase B trigger failure

The number of SCR trigger failures of phase B exceeds the setting value of parameter n603

117

TR3

Phase C trigger failure

The number of SCR trigger failures of phase C exceeds the setting value of parameter n603

118

Fed1

Phase A conduction feedback error

In the standby state, the phase deviation of the feedback signal is too large. Check the optical fiber feedback position, voltage sampling connection position or the corresponding phase driver board feedback signal.

119

Fed2

Phase B conduction feedback error

Same as above

120

Fed3

Phase C conduction feedback error

Same as above

121

Trp

Trigger board power supply abnormality

The trigger board control power supply is out of the range of DC22.0V~42.0V

122

Tend

Start timeout protection

The startup time exceeds the setting value of parameter n616

123

JCEr

Bypass contactor failure

The bypass contactor closing coil current is greater than the nP37 setting value for more than 3 seconds.

124

ACOU

Grid overvoltage

The grid voltage exceeds the protection value (1.15 times the rated voltage)