High Voltage Drive
video
High Voltage Drive

High Voltage Drive

Employing cascaded power cell technology, the RNHV 2000 series high voltage drive directly generates 6kV/10kV output as a high-voltage source inverter. Engineered for maximum operational reliability, ease of use, and superior functionality, this solution is ideal for energy-efficient motor speed regulation in fan, pump, and compressor applications, enhancing production efficiency. All assemblies undergo thorough validation and performance verification prior to shipment, ensuring quality assurance for every delivered unit.

Product Overview

 

Addressing retrofit needs while reducing capital expenditure and project timelines for new installations, the system features a unified architecture that incorporates transformer, power conversion, control, and high-voltage switchgear (with optional bypass) cabinets-all including internal wiring and components.
Installation requires only the connection of HV input/output cables, LV control power, and signal lines.

The RNHV series high voltage drive enables consolidated transport and front-access servicing, streamlining field setup, maintenance, and commissioning. Its DC bus uses metallized film capacitors with integrated mechanical bypass modules, offering enhanced reliability, zero maintenance, and an extended service life compared to electrolytic alternatives. Advanced protection and control capabilities ensure adaptable performance across diverse operating environments, meeting precise speed regulation requirements for industrial processes.

 

Product Features

 

RNHV2000 series High Voltage Drive

 

  • Output Power: Maximum power of 10kV/14,000kW and 6kV/8,000kW.
  • Standard Industrial Design: Supports various voltage levels ranging from 3kV to 13.8kV, suitable for high-altitude, low-temperature, and high-humidity applications.
  • Customization for Customers: Offers customizable functionality and appearance to meet diverse customer requirements.
  • Inverter Type: Voltage-source cascaded multilevel technology with no special requirements for motors or cables, achieving harmonic-free operation without the need for filters. The direct power supply distance can reach up to 1000m.
  • Siemens PLC: Provides safe and reliable precise logic control with standard industrial interfaces.
High Power MV VFD
 

Model Description

 

product-1833-465

 

The components of the RNHV2000 Series

 

 

HV drive

Power Unit Cabinet

 

Innovative Modular Drawer Cabinet Structure

The new cabinet design features a modular drawer structure, allowing for quick plug-and-play connections, as well as convenient installation and maintenance. It combines innovative aesthetics with a lightweight and visually appealing design.

 

Power Unit

 

 

H-Bridge Topology Structure:

Modular design with interchangeable units.

Semi-sealed structure offering strong environmental adaptability and high reliability.

Integrated unit with an internal bypass function.

6KV VFD

 

Perfect Input-output Waveform

MV Drive Cooling

 

product-500-300 product-500-300

High-quality input waveform

Perfect output waveform

  • Multi-pulse rectification eliminates the need for additional power factor correction and harmonic suppression devices.
  • Automatic pre-charge power limits the transformer surge impact.
  • The total harmonic distortion (THD) of the input current is well below the national standard requirement of 5%, while maintaining the inverter's input power factor close to 1, greatly improving the quality of the grid-side power supply.
  • Multi-level superposition for sinusoidal voltage waveform output.
  • Produces a high-quality sinusoidal waveform without torque pulsation caused by harmonic components from frequency converters, even at low speeds.
  • Low dv/dt value, with no special insulation requirements for motors and cables, and no need to replace the motor.

 

Energy-saving and Consumption Reduction 

 

 According to the load characteristic curve, the energy consumption of fans, pumps, and compressors is directly proportional to the cube of the motor speed. For these types of loads, controlling the motor speed is the most effective way to achieve energy savings.

  According to the load characteristic curve, the energy consumption of fans, pumps, and compressors is directly proportional to the cube of the motor speed. For these types of loads, controlling the motor speed is the most effective way to achieve energy savings.

  High voltage drive: By employing more precise, faster, and more flexible motor speed control methods, the overall level of process control can be significantly improved.

 Variable frequency drives (VFDs) have the features of soft starters, which reduce the impact of high currents during motor startup on the power grid (voltage drop). Additionally, compared to soft starters, VFDs can provide greater starting torque and lower starting current, resulting in a more significant reduction in motor winding stress and energy consumption.

 The motor startup and acceleration processes can be effectively controlled, reducing mechanical stress on the user's load.

Compared to operating at the motor's rated frequency, using VFDs results in a higher input power factor.

 VFD energy losses can be as low as 1.5%(excluding transformers)

 

energy saving HV Drive

 

High Reliability

 

 When selecting unit DC capacitors, we choose dry-type metallized electrolytic film capacitors, whereas traditional inverters commonly use aluminum electrolytic capacitors.

The DC capacitors serve to fully isolate the grid from the load through the inverter, eliminating voltage ripple, stabilizing DC voltage, and effectively suppressing disturbances caused by load and grid-side harmonics, as well as switch transients. This results in a longer mean time between failures (MTBF) and improved reliability.

The advantages of using metallized thin film capacitors are as follows:

  • High ripple current handling capability.
  • With their self-repair capabilities, they offer a longer lifespan.
  • Outstanding performance in low temperatures.
  • Operate at high voltage without the need for series connections or polarity, simplifying system design, reducing the impact of stray parameters, and enhancing system stability.

 

Product Technical Specifications

 

Name Item Specification
Input 2000 Series Power
Supply
3-phase, 3.3~11kV, frequency: 50/60Hz
Input voltage range Voltage: -10% to +10%; Frequency: ±2%
Output 2000 Series
Rated Voltage
3-phase 3.3~11kV, frequency: 50/60Hz
Frequency
modulation range
0~50/60Hz
Setting resolution 0.01 Hz
Overcurrent
capability
120% of rated output current for 1 minute every 10 minutes;
150% of rated output current for instantaneous protection.
Control Control method V/F control with PG vector control and without PG vector control.
Synchronous
switching
The frequency converter follows the voltage phase and frequency of the power grid, achieving a state
of grid connection and smooth switching from frequency converter to power frequency without impact
Torque
compensation
Automatic torque boost during startup to reach above 150%.
Slip compensation Compensates for speed drop under load to enhance mechanical robustness.
Upper and lower
frequency limits
Upper and lower frequency limits can be set.
Skip frequency Skip frequency can be set in 3 groups.

 

 Connect the table 

 

Name Item Specification
Control Speed tracking
during restart
The inverter can automatically search for the motor speed and smoothly restart operation when
the motor is coasting due to power loss.
Acceleration and
deceleration time
Acceleration and deceleration time can be independently set from 0.1 to 3600 seconds.
Acceleration and
deceleration profile
types
Linear or S-curve profiles can be selected to meet various application requirements.
Operating modes Local operation, on-site operation, remote operation.
Stopping methods Option to choose between coasting stop or deceleration stop.
PID closed-loop
control
Can be applied to various closed-loop control systems such as flow, pressure, temperature, and
more.
Neutral drift By bypassing a power unit and using neutral drift technology, the three-phase output stays
balanced. This guarantees maximum output power even after bypassing a unit. In case of a
single-unit failure, the system can operate in bypass mode without impacting regular production
operations.
Automatic unit
bypass
When a unit malfunctions, the inverter can automatically bypass the faulty unit and continue oper-
ating using neutral drift technology without the need for manual intervention. If more than two units
are bypassed, users simply need to operate at a reduced capacity as necessary.
Power failure
restart
In the event of an abnormal power outage, the inverter can automatically restart and restore to its
pre-power loss state once the grid is restored within the set time, without the need for manual
intervention.
Frequency setting Analog input signal setting: Configurable via a 4-20mA current signal. Multiple frequency segment
selection settings.
Fieldbus ModbusđTcp/ipaPROFIBUS-DP
Operating state
output signal
Relay output: selectable to indicate operating states such as running, stopped, fault, etc.
Analog output: selectable to indicate operating parameters such as frequency, current, voltage,
speed, etc.
Display During opera-
tion/stop
Display frequency, current, voltage, etc.
During setting Display the set menu number or set parameter value
During functional
operation
Display active function information or prompts.
During alarms,
faults
Display various alarms and faults.
  Overload protection To monitor the output current of the inverter and protect the inverter in case of overload.
Protection
Overvoltage
protection
To detect the overvoltage of the DC busbar unit and protect the inverter in case of input overvolt-
age.
Surge voltage
protection
To monitor surge voltages between input power lines and line-to-ground, protecting the inverter.
Under-voltage
protection
To monitor the input voltage and protect the inverter in case of under-voltage.
Overheat protection To monitor the temperature rise of the heat sink and protect the inverter when it exceeds the set
value.
Short-circuit
protection
To monitor short circuits or overcurrent on the output side of the inverter, protecting the inverter.
Motor overload
protection
To monitor the motor for overload during operation and protect the motor.
Open phase
protection
To monitor the input voltage for phase loss and protect the inverter.
Environment Place of use Indoors, at an altitude below 1000 meters, with no corrosive or flammable gases; free from dust,
oil mist, water droplets, etc., preventing direct sunlight exposure, and without strong magnetic field
interference. Altitudes above 1000 meters require derating for use.
Operating
temperature
- 5℃~ +40℃
Operating humidity 5 ~ 95%RH (non-condensing)
Vibration ≤0.5g
Storage tempera-
ture
- 40℃~+70℃
Ingress protection
rating
IP30 (Please specify other protection ratings when ordering)

 

RNHV2000 Product Selection Table Ⅰ

 

Inverter model Rated
voltage
(kV)
Rated
current
(A)
Motor power
compatibility
(kW)
Output
capacity
(kVA)
Dimensions
(W*D*H mm)
(including fan)
Weight
(kg)
10kV
RNHV-A-10/220 10 16 220 280 3400*1200*2750 3350
RNHV-A-10/250 10 18 250 315 3380
RNHV-A-10/280 10 20 280 350 3400
RNHV-A-10/315 10 23 315 400 3420
RNHV-A-10/355 10 26 355 450 3440
RNHV-A-10/400 10 30 400 500 3460
RNHV-A-10/450 10 32 450 560 3480
RNHV-A-10/500 10 35 500 630 3500
RNHV-A-10/560 10 40 560 700 3600
RNHV-A-10/630 10 45 630 800 3600*1200*2750 3650
RNHV-A-10/710 10 50 710 900 3700
RNHV-A-10/800 10 60 800 1000 3800
RNHV-A-10/900 10 65 900 1120 3800*1500*2750 4200
RNHV-A-10/1000 10 75 1000 1250 4600
RNHV-A-10/1120 10 85 1120 1400 4800
RNHV-A-10/1250 10 90 1250 1600 5000
RNHV-A-10/1400 10 100 1400 1750 5200
RNHV-A-10/1600 10 115 1600 2000 5300
RNHV-A-10/1800 10 130 1800 2250 5500
RNHV-A-10/2000 10 145 2000 2500 4900*1500*2750 6400
RNHV-A-10/2100 10 150 2100 2650 6600
RNHV-A-10/2200 10 160 2200 2750 6800
RNHV-A-10/2240 10 165 2240 2800 7000
RNHV-A-10/2400 10 170 2400 3000 7200
RNHV-A-10/2500 10 180 2500 3150 7400
RNHV-A-10/2800 10 200 2800 3500 7600
RNHV-A-10/3000 10 215 3000 3750 7800
RNHV-A-10/3150 10 225 3150 3940 8000
RNHV-A-10/3550 10 250 3550 4500 5700*1700*2750 10000
RNHV-A-10/3800 10 275 3800 4750 10200
RNHV-A-10/4000 10 280 4000 5000 5900*1700*2750 10400
RNHV-A-10/4200 10 300 4200 5250 10600
RNHV-A-10/4400 10 315 4400 5500 10800
RNHV-A-10/4500 10 320 4500 5600 11000
RNHV-A-10/4800 10 350 4800 6000 6900*1700*3200 14300
RNHV-A-10/5000 10 360 5000 6250 14400
RNHV-A-10/5400 10 390 5400 6750 14500
RNHV-A-10/5600 10 400 5600 7000 14600
RNHV-A-10/6000 10 435 6000 7500 14700
RNHV-A-10/6300 10 460 6300 8000 14800
RNHV-A-10/7100 10 520 7100 9000 8200*1700*3200 16500
RNHV-A-10/8000 10 580 8000 10000 16800
RNHV-A-10/8500 10 600 8500 10625 17000
RNHV-A-10/9000 10 650 9000 11250 8400*1700*3500 22000
RNHV-A-10/9500 10 680 9500 11875 22200
RNHV-A-10/10000 10 710 10000 12500 22400
RNHV-A-10/10500 10 750 10500 13125 22600
RNHV-A-10/11000 10 780 11000 13750 26500
RNHV-A-10/11500 10 820 11500 14375 12400*1700*3500 26700
RNHV-A-10/12000 10 860 12000 15000 26900
RNHV-A-10/12500 10 900 12500 15600 27000
RNHV-A-10/14000 10 1000 14000 17500 27500

 

RNHV2000 Product Selection Table Ⅱ

 

Inverter model Rated
voltage
(kV)
Rated
current
(A)
Motor power
compatibility
(kW)
Output
capacity
(kVA)
Dimensions
(W*D*H mm)
(including fan)
Weight
(kg)
6kV
RNHV-A-6/220 6 26 220 280 2800*1200*2750 2850
RNHV-A-6/250 6 30 250 315 2860
RNHV-A-6/280 6 35 280 350 2880
RNHV-A-6/315 6 40 315 400 2900
RNHV-A-6/355 6 45 355 450 2920
RNHV-A-6/400 6 50 400 500 2940
RNHV-A-6/450 6 55 450 560 2960
RNHV-A-6/500 6 60 500 630 2980
RNHV-A-6/560 6 70 560 700 3000*1200*2750 3000
RNHV-A-6/630 6 75 630 800 3500
RNHV-A-6/710 6 85 710 900 3600
RNHV-A-6/800 6 100 800 1000 3700
RNHV-A-6/900 6 110 900 1120 3800
RNHV-A-6/1000 6 120 1000 1250 3900
RNHV-A-6/1120 6 130 1120 1400 4000
RNHV-A-6/1250 6 150 1250 1600 3800*1500*2800 4700
RNHV-A-6/1400 6 170 1400 1800 5000
RNHV-A-6/1480 6 180 1480 1850 5200
RNHV-A-6/1600 6 190 1600 2000 5300
RNHV-A-6/1800 6 215 1800 2250 5500
RNHV-A-6/2000 6 240 2000 2500 4600*1500*2800 7000
RNHV-A-6/2100 6 250 2100 2650 7200
RNHV-A-6/2200 6 265 2200 2750 7400
RNHV-A-6/2240 6 270 2240 2800 7600
RNHV-A-6/2400 6 275 2400 3000 7800
RNHV-A-6/2500 6 305 2500 3150 8000
RNHV-A-6/2800 6 340 2800 3500 5100*1700*2950 8200
RNHV-A-6/3000 6 360 3000 3750 8400
RNHV-A-6/3150 6 380 3150 3940 8600
RNHV-A-6/3550 6 430 3550 4500 8800
RNHV-A-6/3800 6 470 3800 4750 9000
RNHV-A-6/4000 6 480 4000 5000 9200
RNHV-A-6/4200 6 505 4200 5250 6600*1700*2950 10700
RNHV-A-6/4400 6 530 4400 5500 10900
RNHV-A-6/4500 6 540 4500 5600 11100
RNHV-A-6/4800 6 580 4800 6000 6900*1700*3200 11500
RNHV-A-6/5000 6 600 5000 6300 12000
RNHV-A-6/5400 6 645 5400 6750 6000*1700*3400 14600
RNHV-A-6/5600 6 675 5600 7000 14800
RNHV-A-6/6000 6 725 6000 7500 15000
RNHV-A-6/6300 6 750 6300 8000 8000*1700*3400 18600
RNHV-A-6/7100 6 860 7100 9000 18800
RNHV-A-6/8000 6 900 8000 10000 19000

 

The system specifications are shown in the table above. Please note that the dimensions may vary slightly from the actual size and are provided for equipment selection reference only. For the exact dimensions, please consult our sales personnel.

 

Application Areas

 

product-303-190

Power plant

 

Wind turbine / Compressor / Pumped hydro storage plant / Draft

fan / Condensate pump / Circulating water pump / Boiler feedwater

pump, etc.

product-303-190

Oil, Petrochemicals, Natural gas

 

Pipeline transfer pump / Injection pump / Feedwater pump / Submers-

ible oil pump / Circulating water pump / Brine pump / Compressor /

Booster fan / Oil transfer pump / Electric submersible pump, etc.

product-303-190

Coal, Mining

 

Scale removal pump / Slurry pump / Slag slurry pump / Clear water

pump / Feed pump / Axial flow fan / Agitation pump / Kiln / Transmis-

sion / Dust removal fan / Drainage pump / Media pump / Counter-ro-

tating fan, etc.

product-303-190

Cement building materials

 

Kiln induced draft fan / Kiln forced draft fan / Kiln tail fan / Kiln head

fan / High-temperature fan / Coal mill fan / Dust removal fan / Circu

lating fan / Raw material grinding fan / Cement grinding fan / Separa-

tor fan / Pressure conveying fan, etc.

product-303-190

Steel and metallurgy

 

Blast furnace blower / induced draft fan / compression fan / air

supply fan / feedwater pump / water supply pump / descaling pump /

dust removal fan / converter / blast furnace / etc.

product-303-190

Municipal water supply

 

Aeration blower(for heating, water supply, sewage, etc.) / induced

draft fan / air supply fan / booster pump / hot water circulation pump

/ sewage pump / clean water pump / lift pump / water supply pump /

reclaimed water pump, etc.

product-303-190

Light industry, Chemical industry

 

Coal gas blower / booster pump / compressor / axial flow pump / soft

water pump / water supply pump, etc.

Hot Tags: high voltage drive, China high voltage drive manufacturers, suppliers, factory, inverter variable speed drive, diy vfd, ac vvvf drive, variable frequency drive inverter, 240v 60hz inverter, dc variable frequency drive